BriefDescription
The WRNR-01 thermocouple is specialized in electric powerindustry. With our country, electric power industry development, various thermocoupleis applicable to power plant. Our factory to catch up with the internationalindustrial instruments level, save the country foreign exchange as well,has introduced from abroad the professional manufacturing technology andequipment, and based on original products, widely accepts the design instituteand the opinions of the power users, in accordance with JB/T9238-1999 andJB/T8622-997 standard.
Range and spec
Type Model Graduation Range(℃) Accuracy Allowable error △t
Nickel Chrome-Nickel Silicon WRNT K 0-800 I ±1.5℃ or ±0.004∣t∣
II ±2.5℃ or ±0.0075∣t∣
Nickel Chrome–Copper Nickel WRET E 0-600 I ±1.5℃or ±0.004∣t∣
II ±2.5℃or ±0.0075∣t∣
Copper-Copper Nickel WRCT T -40-350 I ±0.5℃or ±0.004∣t∣
II ±1℃or ±0.75%∣t∣
Hot jacketthermocouple
Name Model Graduation MeasureRange Nominalpressure Flowrate Protectiontube material
Simplex thermocouple WRNR-01 K 0~600℃ ≤29.4MPa ≤100m/s Stainless Steel1Cr18Ni9Ti
WRER-01 E
Duplex thermocouple WRNR2-01 K
WRER2-01 E
Express Lane
- CATEGORIES:
SZD Electric tachometer SZG Digital tachometer SZM Magnetic speed table CZ Fixed magnetic speedometer LZ Fixed speed table HAL Hall speed sensor SZGB Photoelectric speed sensor SZMB Magnetic speed sensor Speed sensor SZJ standard speed generator XBJ Automatic balance recorder XCJ Automatic balance recorder