|
Brief Description
The WRE2-220 assembly thermocouple is used as a sensor tomeasure temperature, usually matched with display instruments, recording meterand electronic regulator. It can directly measure temperature from 0oCto 1800oC of liquid, vapor, gas medium and solid surface duringvarious production processes.
Since1987, according to the national regulations, our factory have been producing thermocouplemade from PtRh30-PtRh6, PtRh10, NiCr-NiSi, NiCr-CuNi, Cu-CuNi, Fe-CuNi etc underthe IEC international standard index numbers, and JB/T9238-1 999 standard aswell.
Category Model Graduation Range Allowable error(△t℃)
Platinum rhodium30-Platinum rhodium6 WRR B 0-1800 ±1.5℃ or ±0.0025∣t∣
Platinum rhodium10-platinum WRP S 0-1600 ±1.5℃ or ±0.0025∣t∣
Nickel chromium-nickel silicon WRN K 0-1300 ±2.5℃ or ±0.0075∣t∣
Nickel chromium-copper nickel WRE E 0-800 ±2.5℃ or ±0.0075∣t∣
Model of WRE2-220 assembly thermocouple
W Temperature meter
R Thermocouple
□thermocouple material R) Platinum rhodium30-Platinum rhodium6
P) Platinum rhodium10-platinum
N) Nickel chromium-nickel silicon
E) Nickel chromium-copper nickel
□ install and fixed type 1) without fixed device
2)fixed thread type
3)movable flange type
4)fixed flange type
5)movable flange with square tube type
6) fixed thread with tapered tube type
□ junction box type 2)splash proof type
3)waterproof type
4)explosion-proof type
□ design series number 0)ø16mm protecting tube
1)ø25mm protecting tube(duplex tubes)
2)ø16mm high aluminum tube(Simplex tube)
3)ø20mm high aluminum tube
Fixed thread thermocouple
Thermocouple Model Graduation Range ℃ Protection casing material Specs Junction box
Total lengthL mm Insert Lengthl mm
Simplex NiCr-NiSi WRN-220 K 0~800 0~1000 1Cr18Ni9Ti 1Cr25Ni20﹟ 300350400450550650900115016502150 150200250300400500750100015002000 Splash-proof type Water-proof type
WRN-220A
Duplex Nicr-NiSi WRN2-220
WRN2-220A
Simplex NiCr-CuNi WRE-220 E 0~600 1Cr18Ni9Ti
WRE-220A
Duplex NiCr-CuNi WRE2-220
WRE2-220A
Simplex NiCr-NiSi WRN-230 K 0~8000~1000 1Cr18Ni9Ti1Cr25Ni20#
Duplex NiCr-NiSi WRN2-230
Simplex NiCr-CuNi WRE-230 E 0~600 1Cr18Ni9Ti
Duplex NiCr-CuNi WRE2-230
Note: 1)Thermal-responsetime-T0.5<911seconds
2) “#” meansthere has no such type material
3) Nominal pressure:10MPa.
Fixed thread specifications
Model Fixed thread specifications
WRN-220 M27×2
WRN-220A G3/4〞
WRN2-220 M27×2
WRN2-220A G3/4〞
WRE-220 M27×2
WRE-220A G3/4〞
WRE2-220 M27×2
WRE2-220A G3/4〞
WRN-230 M27×2
WRN2-230 M27×2
WRE-230 M27×2
WRE2-230 M27×2
Note: Forspecial requirement of the WRE2-220 thermocouple, please contact themanufacturer.